7:30am - 5:30pm Saturday - Wednesday / 7:30am - 1:30pm Thursday / Off - Friday
+971 6 534 0300

Ceiling indoor & outdoor speaker with strobe

Description

Product Description

Speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components. These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 7 field-selectable candela settings for both wall and ceiling speaker strobes. The low total harmonic distortion of the SP speaker offers high fidelity sound output while still offering high volume sound output for use in high ambient noise applications. Its agency listings are UL listed ,FM.

Additional information

Features and Benefits

• Plug-in design and protective cover reduce ground faults
• Universal mounting plate with an onboard shorting spring tests wiring continuity before installation
• No extension ring required
• Field selectable candela settings on ceiling units:
15, 30, 75, 95, 115, 150, and 177
• Automatic selection of 12- or 24-volt operation at 15 and 30 candela
• Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts)
• Speakers offer high fidelity and high volume sound output
• 520 Hz +/- 10% square wave tone capable with compatible FACP
• Compatible with System Sensor synchronization protocol
• Electrical compatibility with existing SpectrAlert and SpectrAlert Advance products
• Tamper-resistant construction
• Updated modern aesthetics

Electrical/Operating Specifications

Nominal Voltage (speakers)
25 Volts or 70.7 Volts (nominal)

Maximum Supervisory Voltage (speakers)
50VDC

Strobe Flash Rate
1 flash per second

Nominal Voltage (strobes )
Regulated 12 voe or regulated 24 VDC/FWR 1·2

Operating Voltage Range (includes fire alarm panels with built in sync)
8 to 17.5 V (12 V nom inal) or 16 to 33 V (24 V nominal)

Operating Voltage with MDL3 Sync Module
8.5 to 17.5 V (12 V nom inal) or 16.5 to 33 V (24 V nominal)

Frequency Range 400 to 4,000 Hz3
Power ¼, ½, 1, 2 watts

Share